L02 · Foundation · 2–3 hours

Hydrostatic pressure

Draw the water-pressure diagram on a vertical face and calculate the resultant and its line of action per metre width.

Tool: Draft · Lesson: Drafted awaiting review · Example: Drafted awaiting review · Workbook: Built awaiting check · Assessment: Drafted awaiting approval

Outstanding before release: Engineering checker to confirm CDC A3 cl. 3.8.3.1 values (10.00 / 10.30 kN/m³) against the PDF page and sign off v0.1.0.

Sources

RoleSourceNote
PrimaryLTA CDC A3 cl. 3.8 GROUND AND WATER LOADSGround and water loads (mapping awaiting checker verification)
PrimaryLTA CDC A3 cl. 3.8.3 (design groundwater levels)Design groundwater levels — the head H must come from here / project criteria (mapping awaiting checker verification)
PrimaryLTA CDC A3 cl. 3.8.3.1 (groundwater and seawater density)Water density values (mapping awaiting checker verification)
SupportingHydrostatics: p = γw·z (fluid statics, any standard fluid-mechanics text)Method source (mapping awaiting checker verification)

"Primary" marks the governing clause for this exercise; "contextual" marks related clauses; "supporting" marks the design-method or data source outside the CDC. A CDC chapter mapping does not mean the CDC contains the equation used.

Prerequisites: F01 Design basis and calculation register · Topics: Loads and actions, Retaining structures, Soil and groundwater

Lesson

Lesson draft v0.1 — awaiting trainer and technical review.

Water pressure governs many underground and retaining-structure checks in Singapore, where groundwater is often near the surface. Before a wall or slab can be designed, someone must draw the water-pressure diagram and give its resultant. A reviewer will first ask where the design water level came from.

Learning outcomes

Model, assumptions and limitations

In still water with a free surface at atmospheric pressure, pressure increases linearly with depth: p(z) = γw·z.

On a vertical face of height H below the free surface, the diagram is a triangle. Base pressure p = γw·H. Resultant per metre width F = ½·γw·H², acting at H/3 above the base (the centroid of the triangle).

The head H is not something the tool chooses. CDC A3 3.8.3 deals with design groundwater levels; the project criteria set the level for each design situation.

Water unit weight: CDC A3 cl. 3.8.3.1 (as read on 1 Nov 2026, awaiting checker confirmation) gives 10.00 kN/m³ for groundwater and 10.30 kN/m³ for seawater. The worked example below uses 9.81 kN/m³ as a stated training assumption so you can see how the choice changes the result.

Worked example — vertical face, 3.0 m head (assumed for training)

  • H = 3.0 m from free surface to base
  • γw = 9.81 kN/m³ (assumed for training)
  • Vertical plane face; atmospheric pressure at top; no seepage
StepSubstitutionResult
Base pressurep = γw·H = 9.81 × 3.029.43 kPa
ResultantF = ½·γw·H² = 0.5 × 9.81 × 9.044.145 kN/m
Line of actionȳ = H/3 = 3.0/31.0 m above base
Same case with CDC A3 groundwater value 10.00 kN/m³p = 30.0 kPa; F = 45.0 kN/m+1.9%

Excludes seepage and project design factors.

Common mistakes

Interpretation questions

Technical English task

A checker writes: "Confirm design groundwater level and density adopted." Draft a reply giving the level, its source clause and the density used.

Burmese explanation: awaiting reviewed translation.

Calculator

Purpose: Hydrostatic pressure distribution, resultant force and line of action on a vertical plane face, per metre width.

Model: Static water, free surface at atmospheric pressure, vertical plane face, head H from free surface to base. p(z) = γw·z; resultant F = γw·H²/2 acting at H/3 above the base.

Units: SI only: H and z in m, γw in kN/m³, pressure in kPa (kN/m²), force in kN per m width. Ranges: 0 < H ≤ 100 m; 0 ≤ z ≤ H; γw 9.5 to 10.5 kN/m³ for project values (outside → outside supported scope).

Equations: p(z) = γw · z ; p_base = γw · H ; F = ½ · γw · H² ; ȳ = H / 3 (above base)

Not covered: Seepage, flow and pore-pressure gradients; Inclined or curved faces; Layered fluids or pressurised surfaces; Wave, dynamic or tidal effects; Design water level selection (user must take the level from project criteria, e.g. CDC A3 cl. 3.8.3); Partial factors and combinations

Version 0.1.0 Draft

Not available for use. Not yet released for use. Status: Draft. Engineering checker to confirm CDC A3 cl. 3.8.3.1 values (10.00 / 10.30 kN/m³) against the PDF page and sign off v0.1.0.

Excel workbook

The workbook is available with the calculator once this version is released.

Exercises

L02-EX1 — Basement wall water pressure

Drafted — awaiting approval of the brief, rubric and pass mark before submissions open.

About this academy. Exercises use fictional or permission-cleared data and are simulated training, not supervised project experience. Completing modules does not confer professional registration, LTA approval or recognised Singapore working experience, and does not guarantee employment. Calculators produce preliminary outputs for learning and checking; they are not PE-endorsed designs. Official requirements are in the documents published by LTA and other issuing bodies — always use the edition your contract specifies.